OVER CURRENT RELAY BROYCE CONTROL P9670 P-9670 P 9670 OCR 253PAPW OCR 253 PAPW - GENUINE UK
INDENT = 25 HARI
Part Number : P9670
Overcurrent detection (IDMT)
6 Selectable IDMT curves
Programmable Low-set and High-set tripping thresholds
LCD with live display of individual phase currents
Last trip memory/history recall
Pre-defined selectable CT ratio’s
Test and Reset buttons
96 x 96mm, Panel Mount
Fully programmable and easy to set-up digital relay that offers the user the ability to monitor and detect an Overcurrent condition of each phase. The user is able to choose from 6 tripping characteristics curves or alternatively assign a Definite Time. Two separate relay outputs are provided and can be configured to either operate at the beginning or end of a time out period and additionally, set for Manual or Auto-resetting.
A clear, backlit LCD provides all key information the user requires for both operation and setting up.
An auxiliary supply (required to power the unit) must be present for the product to function.
SPECIFICATIONS
Monitoring function: Overcurrent
Characteristic curves: NI 3/10, NI 1.3/10, Long Time Inverse, Very Inverse, Extremely Inverse, Extremely Inverse 0.65
Low-set trip threshold: 0.5 – 10A
High-set trip threshold: 0.5 – 100A
Aux. supply voltage*: 18 – 55VAC/18 – 72VDC or 85 – 265VAC/85 – 370VDC
Output: 2 x SPDT 8A @ 250V (AC1)
Dimensions(mm): W:96 x H:96 x D:100
Product standard(s): IEC 60255-151